Back to the list of connectors[1]

Generic UPS

Description

This connector enables hardware monitoring for MIB-2 Standard UPS through an SNMP interface.

datacenter[2] hardware[3]

Source[4]

Target

Typical platform: Any UPS which supports UPS-MIB (RFC1628)

Operating system: Out-Of-Band

Prerequisites

Leverages: N/A

Technology and protocols: SNMP

This connector is not available for the local host (it is applicable to remote hosts only).

Examples

CLI

metricshub HOSTNAME -t management -c +GenericUPS --snmp v2c --community public

metricshub.yaml

resourceGroups:
  <RESOURCE_GROUP>:
    resources:
      <HOSTNAME-ID>:
        attributes:
          host.name: <HOSTNAME> # Change with actual host name
          host.type: management
        connectors: [ +GenericUPS ] # Optional, to load only this connector
        protocols:
          snmp:
            version: v2c # Read documentation for v1, v2c and v3
            community: public # or probably something more secure

Connector Activation Criteria

The Generic UPS connector will be automatically activated, and its status will be reported as OK if all the below criteria are met:

  • An SNMP Get-Next on the OID 1.3.6.1.2.1.33 must return a value in the same subtree

Metrics

Type Collected Metrics Specific Attributes
battery
  • hw.battery.charge
  • hw.battery.time_left
  • hw.status{hw.type="battery", state="degraded|failed|ok"}
  • hw.status{hw.type="battery", state="present"}
  • hw.parent.type
  • id
  • name
  • type
enclosure
  • hw.enclosure.energy
  • hw.enclosure.power
  • hw.status{hw.type="enclosure", state="degraded|failed|ok"}
  • hw.status{hw.type="enclosure", state="present"}
  • id
  • info
  • model
  • name
  • type
  • vendor
temperature
  • hw.status{hw.type="temperature", state="present"}
  • hw.temperature
  • hw.temperature.limit{limit_type="high.critical"}
  • hw.temperature.limit{limit_type="high.degraded"}
  • hw.parent.type
  • id
  • name
  • sensor_location
voltage
  • hw.status{hw.type="voltage", state="present"}
  • hw.voltage
  • hw.voltage.limit{limit_type="high.degraded"}
  • hw.voltage.limit{limit_type="low.critical"}
  • hw.parent.type
  • id
  • name
  • sensor_location
No results.